18-4 |  Table Reference Cable 

Correctional Factor: Ambient Temperature (Ca)

Correctional Factor:  Cable Grouping Factor (Cg)

Correctional Factor:   Thermal Insulation Factor (Ci) 


Table: 4D1A  |  Current Carrying Capacity of Conductor

Source:    IEE Wiring Regulation (16th Edition)  Table 4D1B 

Table 4D1B  |  Voltage Drop Properties of Conductor

Source:    IEE Wiring Regulation (16th Edition)  Table 4D1B

Table 54G  |   Sizing of Protective Conductor (S)

Source:    IEE Wiring Regulation (16th Edition)   

 This sizing of protective conductor is apply upon phase conductor size in (mm²)

Phase Conductor          |    Protective conductor (E)       |    Example                                                                  ____________

      <16.0 mm²                    Same or 1:1                                    When RYBN is 10.0 mm² then E shall be 10 mm²

      16 ~ 35 mm²                  Fixed 16mm²                                When RYBN is 30.0 mm² then E shall be 16 mm²

      > 35.0 mm²                    1/2 size                                          When RYBN is 75.0 mm² then E shall be 35 mm²