16 |  Consumer Earthing

About consumer earthing 

The conductor that connects the exposed metallic parts of the consumer's electrical installation is called protective earth. 

Consumer earthing a commonly applied on to residential houses, shops, buildings, and factories. 

 Mandatory as protection 

When there is a fault in electrical system it is very important to protect any person from electrocution.  According to Electricity Regulations, it is required to install earthing systems or methods of grounding on electrical supply system.

Component of earthing 

Earthing requirement 

Earthing methods  

There are various methods for earthing. 

Method 1:   Single rod 

Refer to figure on the right, this method is commonly installed on to  houses, shops and buildings. 

The main earth conductor size shall be same sized as phase conductor. 

Example if the phase conductor is 16mm.sq then the earth rod shall be 16.0mm. diameter at length of at least 3 meter.  

For Reference

Method 2:   multiple earth chamber 

Refer to figure on the right, this method is commonly installed on to buildings or factories system. 

This due to poor earth resistance and this method allows additional earth chamber to bring down the total earth resistance value to one ohm or lower. 

For Reference 

Method 3:   Wire mesh 

Refer to figure on the right, this method is suited for power substation.

The value of this mesh configuration must be below one(1) ohm. The voltage applies on substation can be greater than 500 volts in certain areas or site. 

For Reference 

Method 4:   Copper plate 

Refer to figure on the right, this method is suited for high voltage pylon tower (HT overhead lines).

The depth of this copper plate installation must be at least 15 meter or greater depending on soil at site.

For Reference 

Earth resistance 

Earth value of earth conductor connected with the ground or earth must be achieved as low resistance possible. This is a purpose to allow any fault current (leakage current) from electrical loads can allow these current to quickly flow to the ground. The ground acts as absorbing any current from faulty electrical equipment by preventing any person from electrocution.  

Earth resistance value can be tested with a test set known as earth resistance test (or ground testset).

Formula earth resistance 

Re = (Z + Z1 + Z2) ÷ 3 

where

Z   - point 1 measured value

Z1 - point 2 measured value

Z2 - point 3 measured value 


In order to achieve lowest resistance value, the depth of the main earth conductor shall be at least 3 meter.

Example earth resistance calculation

Solution:     Re = (Z + Z1 + Z2 ) ÷ 3  

          Re = ( 1.1Ω + 0.5Ω + 0.8Ω ) ÷ 3  =  0.8Ω     GOOD earth value

What if earth resistance is greater than 1Ω ? 

Certain places where the ground is dry and hard or sometimes may have rocks on the ground. When such conditions happen you may not able to achieve a good earth resistance value. Therefore you may need to reposition the earth chamber or find another soft ground spot. 

Solution: 

Sizing of Protective Conductor 

According IEE Wiring Regulation on Table 54G Sizing of conductor

Phase conductor size (mm²)         Protective conductor (mm²)   Example

RYBN is <16           1:1  or same   When RYBN is 10mm² then E shall be 10mm²

RYBN is 16 ~35                               Fixed at 16mm²                                           When RYBN is 30mm² then E shall be fixed 16mm²

RYBN is >35                                   Shall be 1/2 of phase conductor                When RYBN is 75mm² then E shall be 35mm² 

More information about earth resistance test can be found on this  topic page